3 Phase Power Distribution of Step-Down Transformer
Verified
Added on Β 2023/06/11
|7
|1228
|363
AI Summary
This article explains the construction and connections of 3 phase transformers for step-down voltage. It includes phasor diagrams and readings for star-delta and star-star connections with different loads. Technical definitions and equations are also provided.
Contribute Materials
Your contribution can guide someoneβs learning journey. Share your
documents today.
3power distribution of the step-down transformerβ The three phase transformer could be formed by three single phase transformers connected to an individual laminated core (Chunlai & Xiaoku, 2011). They have a separate magnetic circuit, which are inter-connected so that a uniform distribution of magnetic flux could be produced (Xinchang & Fengquan, 2010). Hence due to this type of construction they could operate at high and low voltages and the only exception is the shell type of transformer since they are not inter- connected. They are cost effective and the three phase winding could be seen in the figure given below. Figure 1: Construction of three phase transformer Group 1: Star- Delta connection with load 20 ohms: In this type, the primary side is connected like a star and the secondary type is connected like a delta (Keping, Daozhuo & Pengfei, 2012). Usually we use different symbols and alphabets to differentiate the start and delta connections. Normally the primary side could be denoted by the uppercase letters such as R, Y and B (the phases are differentiated by different colors especially red, yellow and blue) and the secondary side could be indicated by the lower case alphabets. Certain technical definitions should be known while dealing with the transformer. The Line voltage is referred as a voltage between any line and the phase voltage is referred as the voltage among any line and the neutral point of the transformer (Jing, Xin & Liqiang, et al., 2013). This phase voltage is equal to 1/β3 times that of the line voltage. This could be represented as, VP= 1/β3 VL
Secure Best Marks with AI Grader
Need help grading? Try our AI Grader for instant feedback on your assignments.
Every relevant secondary winding will have the same voltage induced in it. Since the secondary windings are delta connected, the line voltage will be 1/β3 VL. The Turns ratio could be represented as the ratio between the primary winding NPand the secondary winding NS. This could be denoted by the following equation Turns ratio (n) = NP/ NS For the star- delta connection this could be written as, Turns ratio (n) = VP/β3 VL If the transformer is provided with the same number of windings in the primary and the secondary winding of 1:1 ratio then β3:1 is the step-down line voltage ratio. The line voltage will VL= n VL/ β3 and the line current will be IL= β3. IL/n. the transformation ration (K) is defined as the ratio between the secondary phase voltage and the primary phase voltage (Lin, Yi & Ke, et al., 2012). Since the primary side is star connected, we could need only few numbers of turns. This could be used efficiently for the high voltage step-down transformers. The impedance of each phase could be calculated byZp=.The connection between primary and secondary winding and the phasor diagram connection is shown in the figure given below. Figure 2: Transformer connection β star-delta network
Figure 3: Phasor diagram of star- delta connection Table 1: Readings taken for star- delta connection at load of 20 ohms Group 2: Star-Star connection with the load 10 ohms:
In this type both the primary and the secondary sides are connected in the star with the phase angle of 120 degrees that is out of phase with the rest two phases. The primary winding is magnetically linked with the other secondary winding with the common core leg. In this connection the windings are terminated to a neutral connection point. This neutral part could be grounded or not grounded based on the required specification (Lin, Yi & Ke, et al. (2012). Although the exciting voltage is sinusoidal, the magnetizing current of the transformer is not purely sinusoidal, since they have sufficient amount of odd harmonic component. Suppose when the identical transformers are connected, which is energized by a particular frequency of equal magnitude voltage level (say 60 Hz), the current could be revoked at the neutral. This is because the vector sum of the current could be zero due to their phase angle held at 120 degrees. Anyways the third, sixth and so on harmonics tends to remain in-phase and hence they wonβt cancel out each other. These are said to be known as the zero harmonics. In this situation we tend to have a neutral current. The B-H curve of the star-star connection is said to be non-linear. This could lead to the situation of sinusoidal induced voltages to be supported by odd-harmonics magnetizing currents. Due to the star connection we have lesser turns for windings in which phase voltage are 1/β3 times the line voltage. The phase current is same as the line current due to the star connection, i.e., IP= IL. The phasor diagram of the star-star connection is shown in the figure given below Figure 4: Phasor diagram of star-star connection
Paraphrase This Document
Need a fresh take? Get an instant paraphrase of this document with our AI Paraphraser
Table 2: Readings taken for star- star connection at load of 10 ohms Group 3: Star- Star connection with the load 20 ohms: The connection is same as seen above and the only difference is that the load voltage and the load current could increase in this case. Here the load is connected in the delta mode. Table 3: Readings taken for star- star connection at load of 20 ohms
References: Chunlai, L. & Xiaoku, Y. (2011). Grid-connected technology of solar energy and wind energy[M]. Beijing: ChinaWater Conservancy and Hydropower Press, 158-164. Xinchang, Z. & Fengquan, Z. (2010). Smart grid leads the journey to innovative smart home and energy consumption patterns.Power System Protection and Control.42(5), 59-67. Keping, Z., Daozhuo, J. & Pengfei, H. (2012). Study on a new type of DC distribution network containing electric vehicle charge station.Power System Technology. 36(10), 35-41. Jing, Y., Xin, X. & Liqiang, Z., et al. (2013). A review of low voltage DC power distribution system[J].Proceedings of the CSEE. 33(7), 42-52. Lin, Z., Yi, Z. & Ke, G., et al. (2012). Development of photovoltaic grid-connected system with power quality regulatory function.Power System Protection and Control. 40(9), 137-145.
Haifeng, L., Yanchuang, F. & Zixing, L., et al. (2013). Research on low voltage ride through of photovoltaic plant based on deadbeat control[J]. Power System Protection and Control. 41(21), 110-115.