Task 1
The report shows assessment of a residential building having basement of two storey meant for
carpark and above it five storey for residential. The main aim of this paper would be to identify
the non-compliance issues as per the proposed Deemed – to – satisfy (DTS). Building Code of
Australia provision and recommended compliance provided to overcome non-compliances.
The list of provided Deemed – to – Satisfy that would require to be addressed through alternative
solution, designed amended and additional of information would include:
BCA Clause Provision of Deemed-to-Satisfy that needs to be addressed
C2.6
Separation of
external walls
vertical
openings
Non-compliances locations includes:
Northern Elevation
Existence of horizontal construction at level 3 – 6 whose extension is less than
450 mm past the openings
Eastern elevation
Existence of horizontal construction at level 3 – 6 whose extension is less than
450 mm past the openings
Deemed–to–Satisfy (DTS) | Task Report_1
D1.4
Traveling exit
distances
Travelling distance extended inside the carpark is 40.163 millimeters from the
corner of the right-hand carpark both in basement 1 and basement 2.
It is recommended that the fire engineers would provide suitable points in
different directions based on the reference corners adjacent carpark in respect
to basement 1 and basement 2.
Level 3
The travelling distance path to the point of exit is more than six meters, being
8.017 m, therefore fire engineer would be required to recommend on the
performance solution.
Deemed–to–Satisfy (DTS) | Task Report_2
Level 4 – 6
The travelling distance path to the point of exit is more than six meters, being
7.725 m, therefore fire engineer would be required to recommend on the
performance solution
D1.5
Alternative
exits distance
The alternative exit distance in basement 2 is greater than 60 meters, being
80.09 m.
Deemed–to–Satisfy (DTS) | Task Report_3
The alternative exit distance in basement 2 is greater than 60 meters, being
75.19 m.
Point to note: The alternative exit distance is measured through the selected
point.
Fire engineer would be required to recommend on the performance solution.
D1.7
Travel through
isolated fire
exits.
Discharge from isolated stairways would impose a 6 m passing at any section
of the external wall. It would proper for the wall to have FRL more than
60/60/60 and internally protected openings based to C3.4
Deemed–to–Satisfy (DTS) | Task Report_4

End of preview

Want to access all the pages? Upload your documents or become a member.

Related Documents
Compliance Report of Residential Apartment
|9
|1620
|107

Building Regulations Assignment
|6
|1489
|428

Building Regulation Studies Assignment Report
|5
|803
|26

CCPCCB5001B | Construction of a Medium Building : Codes and Standards
|12
|1872
|13

Building Assessment and Regulation Report
|17
|2508
|414

Fire Safety Design for Buildings and Protection
|13
|3512
|357