Experiment Title: Cooling and dehumidification of air using air conditioning Process Name: Tan Suker ID: 1804645 Group: P4 Date: 11 April 2021 Objectives: (1) To be familiar with Psychrometric chart for cooling and dehumidifying process. (2) To be able to determine the thermodynamic properties of air such as dry bulb temperature, specific humidity (moisture content), relative humidity, specific volume and enthalpy by using Psychrometric chart.
Secure Best Marks with AI Grader
Need help grading? Try our AI Grader for instant feedback on your assignments.
Experiments: Identify the major working parts of the setup in the following diagram and discuss the process of cooling and dehumidifying in brief Figure 1 : Air conditioning Unit with base refrigeration system Two major sections make up the refrigeration unit. The two sections are the base refrigeration unit & air conditioning unit respectively.
The base refrigeration unit is made up of 4 main components. These components are the evaporator, expansion valve, condenser and compressor. The base refrigeration unit runs of the principle of a refrigeration cycle. The refrigeration cycle starts and ends at the compressor. The refrigerant used in the experiment is R-14a. Refrigerant flows into the compressor where it is compressed to a high- pressure gas, causing the temperature to rise. The hot gas then flows into the condenser where it is cooled down by the exterior air or water to become a hot liquid. The liquid refrigerant then enters an expansion valve where it cools down due to the pressure drop, resulting in a cold refrigerant. The cold refrigerant from the expansion valve then enters the evaporator. It enters as a liquid state where heat exchange takes place with the exterior air or water and therefore cooling the load inside the refrigerator. As the liquid cools down the load, heat is absorbed turning it back into a gaseous state. The gas is them pushed back into the compressor where the cycle will repeat again.
In the air conditioning unit, hot air will be flowing through the air inlet to the evaporator coils which has a low temperature due to the cold refrigerant. Heat exchange takes place where the heat from the inlet air is transferred into the evaporator, cooling the air inside the evaporator. As the air reaches dew point, water will start condensing. The condensed air is then collected into a reservoir to be removed. As the air flows out of the evaporator, temperature and relative humidity sensors are installed to check the air to ensure it reaches the target temperature and humidity. If it does not meet the selected criteria, an air heater and humidifier tank is installed such to condition the air further. Before the air escapes through the outlet, another sensor is installed to check the air one last time. If the air still has not met the selected criteriaโs, it will be redirected again into the evaporator to repeat the process to ensure correct air conditioning has taken place.
Paraphrase This Document
Need a fresh take? Get an instant paraphrase of this document with our AI Paraphraser
Discussion: In this experiment, by only looking at the enthalpy, h values before and after the evaporator which are hB/hCand h4/h1respectively, we can see that there is a big difference between the values taken from the psychrometric chart and from steam table. For hBfrom psychrometric chart, the value is 46 kJ/kg and hCis 70kJ/kg. While for the value taken from steam table, h4is 87.396 kJ/kg and h1is 234.44 kJ/kg. The percentage error is given by 83.67%, this shows that the difference between experimental value and theoretical value is big. The difference in enthalpy values may be caused by several factors, one of the factors is that the piping system of the apparatus. For the ideal case, it assumed that there are no losses of energy, so the value we obtain will be higher when compared to experimental value. Besides that, there is also heat lost to the surrounding through conduction. Due to that, heat lost is not equal to the heat gain by the refrigerant, causing heat lost is greater than the heat gain. Coolinganddehumidificationprocessesoccurattheevaporator.Beforeenteringthe evaporator, the air has a temperature of 26.3oC and relative humidity of 78.9%. After entering the evaporator, the air temperature becomes 19.2oC and relative humidity has reduced to 73.9%. This clearly shows that cooling and dehumidification process took place. With the humidity ratio, ฯ and the specific volume, v obtained from the psychrometric chart, we are able to calculate the mass flow rate of the air. With that, we can use the equation mฬ (ฯ1 โ ฯ2) to find the amount of water vapour removed. Given that it is an ideal refrigeration case, we can use the steam table to find the enthalpy, h4and h1. With all the values obtained from the steam table, the cooling load can be obtained from the difference of the enthalpies.
Secure Best Marks with AI Grader
Need help grading? Try our AI Grader for instant feedback on your assignments.
Conclusion In conclusion, the psychometric chart is very important in analysing the properties of air in the refrigeration cycle. By only using the dry bulb temperature and relative humidity, we may be able to obtain the specific humidity (moisture content), specific volume and enthalpy. Besides that, cooling and dehumidifying processes can be easily tracked using the psychometric chart. The difference between theoretical and experimental values is given by a percentage error of 83.67%. This huge difference in values is due to the theoretical values are obtained based on an ideal refrigeration cycle.