This report assesses the compliance of a proposed project at 900 Pacific Hwy & Fitzsimons Lane, Gordon, NSW, with the NCC Building Code of Australia 2016. It identifies areas meeting the 'deemed to satisfy' provisions and those requiring alternative performance-based solutions, particularly concerning fire safety and structural integrity. The report highlights the need for further documentation on aspects like door hardware and service configuration. It addresses structural requirements according to AS/NZS 1170.1 and AS1288/AS2047, fire resistance as per BCA 2016, accessibility and evacuation strategies, and essential services and equipment, including smoke hazard management and lift provisions. Deviations from DTS arrangements, especially regarding travel distances to exits, are noted, suggesting the necessity of a fire engineering assessment for construction certification. The document is for academic purposes and available on Desklib, a platform for student resources.

SCHOOL OF COMPUTING, ENGINEERING AND MATHEMATICS
GROUP ASSIGNMENT COVER SHEET
STUDENT DETAILS
Student name: Student ID number:
Student name: Student ID number:
Student name: Student ID number:
UNIT AND TUTORIAL DETAILS
Unit name: Building Regulation Studies Unit number: 300885
Tutorial/Lecture: Class day and time:
Lecturer or Tutor name: Mr. Roneel Prasad
ASSIGNMENT DETAILS
Title: Assignment 2 – Building Regulations Report 2019
Length: Due date: Midnight 1/2/2019 Date submitted:
Home campus (where you are enrolled):
DECLARATION
I hold a copy of this assignment if the original is lost or damaged.
I hereby certify that no part of this assignment or product has been copied from any other student’s work
or from any other source except where due acknowledgement is made in the assignment.
I hereby certify that no part of this assignment or product has been submitted by me in another
(previous or current) assessment, except where appropriately referenced, and with prior
permission from the Lecturer / Tutor / Unit Coordinator for this unit.
No part of the assignment/product has been written/produced for me by any other person
except where collaboration has been authorized by the Lecturer / Tutor /Unit Coordinator
concerned.
I am aware that this work will be reproduced and submitted to plagiarism detection software programs for
the purpose of detecting possible plagiarism (which may retain a copy on its database for future
plagiarism checking).
Student’s
signature:
Student’s
signature:
Student’s
GROUP ASSIGNMENT COVER SHEET
STUDENT DETAILS
Student name: Student ID number:
Student name: Student ID number:
Student name: Student ID number:
UNIT AND TUTORIAL DETAILS
Unit name: Building Regulation Studies Unit number: 300885
Tutorial/Lecture: Class day and time:
Lecturer or Tutor name: Mr. Roneel Prasad
ASSIGNMENT DETAILS
Title: Assignment 2 – Building Regulations Report 2019
Length: Due date: Midnight 1/2/2019 Date submitted:
Home campus (where you are enrolled):
DECLARATION
I hold a copy of this assignment if the original is lost or damaged.
I hereby certify that no part of this assignment or product has been copied from any other student’s work
or from any other source except where due acknowledgement is made in the assignment.
I hereby certify that no part of this assignment or product has been submitted by me in another
(previous or current) assessment, except where appropriately referenced, and with prior
permission from the Lecturer / Tutor / Unit Coordinator for this unit.
No part of the assignment/product has been written/produced for me by any other person
except where collaboration has been authorized by the Lecturer / Tutor /Unit Coordinator
concerned.
I am aware that this work will be reproduced and submitted to plagiarism detection software programs for
the purpose of detecting possible plagiarism (which may retain a copy on its database for future
plagiarism checking).
Student’s
signature:
Student’s
signature:
Student’s
Secure Best Marks with AI Grader
Need help grading? Try our AI Grader for instant feedback on your assignments.

signature:
Note: An examiner or lecturer / tutor have the right to not mark this assignment if the above declaration has
not been signed.
Note: An examiner or lecturer / tutor have the right to not mark this assignment if the above declaration has
not been signed.

Executive Summary
We have audited structural plan archives arranged by Tecks Designers (allude supplement A) for
consistence with the NCC - Building Code of Australia 2016. This record names significant BCA
prescriptive ('considered to fulfil') arrangements together with regions in which a substitute execution based
arrangement should be created to agree to the execution prerequisites of BCA. The fire wellbeing designed
arrangements relating Category 2 things must be alluded to the NSW Fire Brigade as a feature of
Construction Certificate process. Beginning counsel with the fire detachment will be required amid the
improvement of FEB at plan improvement/construction testament arrange.
The fire built arrangement identifying with class 2 things should be endorsed after conference with the NSW
Fire Brigade as a major aspect of Construction Certificate process. The documentation will require further
specifying, for example, entryway equipment, particulars, and benefit configuration. Nothing in this report
blocks an improvement assent being issued as the proposed fabricating by and large conforms to the DTS
arrangements of BCA 2016. Take-offs from the DTS arrangements will be appropriately tended to by a fire
designing appraisal. The application for Construction Certificate will be surveyed under the important
arrangements of Environmental Planning and Assessment Act 1979 (As Amended) also, the Environmental
Planning and Assessment Regulation 2000.
1.2 Current Legislation
The material enactment overseeing the plan of structures is the Environmental Arranging and Assessment
Act 1979. This Act necessitates that all new building works must be intended to conform to the BCA. The
variant of CA appropriate to advancement is rendition that set up at the season of application to the
Certifying expert for the Construction Endorsement. For the reasons for this evaluation it is expected that
Version of BCA appropriate will be BCA 2016 which comes into power from 1 May 2016.
Question 2: Structure
900 Pacific Hwy & Fitzsimons Lane, Gordon 2072 works are to agree to the pertinent necessities of
AS/NZS 1170.1. Coating is to consent to AS1288, and AS2047.
We have audited structural plan archives arranged by Tecks Designers (allude supplement A) for
consistence with the NCC - Building Code of Australia 2016. This record names significant BCA
prescriptive ('considered to fulfil') arrangements together with regions in which a substitute execution based
arrangement should be created to agree to the execution prerequisites of BCA. The fire wellbeing designed
arrangements relating Category 2 things must be alluded to the NSW Fire Brigade as a feature of
Construction Certificate process. Beginning counsel with the fire detachment will be required amid the
improvement of FEB at plan improvement/construction testament arrange.
The fire built arrangement identifying with class 2 things should be endorsed after conference with the NSW
Fire Brigade as a major aspect of Construction Certificate process. The documentation will require further
specifying, for example, entryway equipment, particulars, and benefit configuration. Nothing in this report
blocks an improvement assent being issued as the proposed fabricating by and large conforms to the DTS
arrangements of BCA 2016. Take-offs from the DTS arrangements will be appropriately tended to by a fire
designing appraisal. The application for Construction Certificate will be surveyed under the important
arrangements of Environmental Planning and Assessment Act 1979 (As Amended) also, the Environmental
Planning and Assessment Regulation 2000.
1.2 Current Legislation
The material enactment overseeing the plan of structures is the Environmental Arranging and Assessment
Act 1979. This Act necessitates that all new building works must be intended to conform to the BCA. The
variant of CA appropriate to advancement is rendition that set up at the season of application to the
Certifying expert for the Construction Endorsement. For the reasons for this evaluation it is expected that
Version of BCA appropriate will be BCA 2016 which comes into power from 1 May 2016.
Question 2: Structure
900 Pacific Hwy & Fitzsimons Lane, Gordon 2072 works are to agree to the pertinent necessities of
AS/NZS 1170.1. Coating is to consent to AS1288, and AS2047.

Preceding the issue of Construction Certificate basic affirmation is required to be given (Allouhi, El Fouih,
Kousksou, Jamil, Zeraouli and Mourad, 2015).
Question 3: Fire Resisting Construction
The structure has been constructed for the most part as per Table 3 of Particular C1.1 of Building Code of
Australia 2016. The building is required to be Type A Construction.
The building has been surveyed based on the accompanying flame partition/ compartmentation inside the
improvement;
Bounding construction to the sole inhabitance units and open halls must accomplish a FRL of at the very
least an hour and a half to loadbearing and an hour for non-loadbearing construction;
Separation between the car park levels and the retails segments of 180 minutes,
Fire compartmentation of building at each floor level,
Rooms opening into open hallways being fire-isolated with construction that accomplish a FRL of at the
very least -/60/an hour for non-loadbearing construction.
Imperviousness to fire levels for building auxiliary individuals is as per the following:
Retail Portions 180 minutes
Car leave levels 120 minutes
Residential Levels an hour and a half
A fire designing appraisal will be produced to decrease the FRL of building components inside the retail
levels to lessen from 180 minutes to 120 minutes.
Fire Separation between Buildings
Building L and M (Lot 104) is associated by means of underground connect to Building J and K.
The openings at the edge limit are fire-isolated by affirmed fire screen.
Every one of structures on Lot 104 and Lot 105 can be gotten to as a different building.
A piece of a building isolated from the rest of building by a fire divider may be treated as a different
building for the motivations behind the DTS arrangements of Section C, D and E (Rasmussen, 2018). In the
event that construction of firewall reaches out through all accounts and spaces that are normal to part and
any abutting piece of building with any openings appropriate secured as per Part C3 of BCA
Kousksou, Jamil, Zeraouli and Mourad, 2015).
Question 3: Fire Resisting Construction
The structure has been constructed for the most part as per Table 3 of Particular C1.1 of Building Code of
Australia 2016. The building is required to be Type A Construction.
The building has been surveyed based on the accompanying flame partition/ compartmentation inside the
improvement;
Bounding construction to the sole inhabitance units and open halls must accomplish a FRL of at the very
least an hour and a half to loadbearing and an hour for non-loadbearing construction;
Separation between the car park levels and the retails segments of 180 minutes,
Fire compartmentation of building at each floor level,
Rooms opening into open hallways being fire-isolated with construction that accomplish a FRL of at the
very least -/60/an hour for non-loadbearing construction.
Imperviousness to fire levels for building auxiliary individuals is as per the following:
Retail Portions 180 minutes
Car leave levels 120 minutes
Residential Levels an hour and a half
A fire designing appraisal will be produced to decrease the FRL of building components inside the retail
levels to lessen from 180 minutes to 120 minutes.
Fire Separation between Buildings
Building L and M (Lot 104) is associated by means of underground connect to Building J and K.
The openings at the edge limit are fire-isolated by affirmed fire screen.
Every one of structures on Lot 104 and Lot 105 can be gotten to as a different building.
A piece of a building isolated from the rest of building by a fire divider may be treated as a different
building for the motivations behind the DTS arrangements of Section C, D and E (Rasmussen, 2018). In the
event that construction of firewall reaches out through all accounts and spaces that are normal to part and
any abutting piece of building with any openings appropriate secured as per Part C3 of BCA
Secure Best Marks with AI Grader
Need help grading? Try our AI Grader for instant feedback on your assignments.

Security of Openings
The prescriptive arrangements of BCA stipulate that openings inside building components required to have a
FRL will be secured as pursues:
1. Any outside opening inside 3m of fire source highlight ensured by -/60/ - fire evaluated construction, or
remotely found divider wetting sprinklers, or an interchange arrangement be given to confirm CP2 of BCA
(Zhang, Wan, Ng and Yang, 2018).
Open Corridors: Class 2 Buildings
Open hallways surpassing 40m long are required to be partitioned into interims of not more than 40m by
smoke evidence dividers.
The length of general population passages to Block L1 has been estimated approx. 41m in lieu of 40m. This
take-off from the DTS can be address by an elective arrangement from a fire build at construction
endorsement organize.
Passive Fire Protection
Other inactive fire security issues that should be tended to in nitty gritty documentation stage include:
Lift engine rooms,
Emergency control supply,
Emergency generators,
Electricity supply,
Boilers or batteries,
Hydrant Pump rooms,
Sprinkler Pump Rooms,
To be isolated from the rest of building by construction accomplishing a least imperviousness to fire
dimension of 120 minutes
Fire Hazard Properties
The fire danger properties of settled surface linings and mechanical ventilation work will likewise be tended
to inside the point by point documentation stage compliant with determination C1.10 Building Code of
Australia (Ashworth and Perera, 2015).
The prescriptive arrangements of BCA stipulate that openings inside building components required to have a
FRL will be secured as pursues:
1. Any outside opening inside 3m of fire source highlight ensured by -/60/ - fire evaluated construction, or
remotely found divider wetting sprinklers, or an interchange arrangement be given to confirm CP2 of BCA
(Zhang, Wan, Ng and Yang, 2018).
Open Corridors: Class 2 Buildings
Open hallways surpassing 40m long are required to be partitioned into interims of not more than 40m by
smoke evidence dividers.
The length of general population passages to Block L1 has been estimated approx. 41m in lieu of 40m. This
take-off from the DTS can be address by an elective arrangement from a fire build at construction
endorsement organize.
Passive Fire Protection
Other inactive fire security issues that should be tended to in nitty gritty documentation stage include:
Lift engine rooms,
Emergency control supply,
Emergency generators,
Electricity supply,
Boilers or batteries,
Hydrant Pump rooms,
Sprinkler Pump Rooms,
To be isolated from the rest of building by construction accomplishing a least imperviousness to fire
dimension of 120 minutes
Fire Hazard Properties
The fire danger properties of settled surface linings and mechanical ventilation work will likewise be tended
to inside the point by point documentation stage compliant with determination C1.10 Building Code of
Australia (Ashworth and Perera, 2015).

2. Infiltrations through flame evaluated floors to be secured either by a tried model (for example fire
neckline, fire damper, and so on.) or be introduced inside a fire evaluated shaft accomplishing the required
FRL;
3. Any infiltration through a divider or room required to have a FRL (for example substation, engine
compartment, condo isolating divider and so forth.) is to be secured either by a tried model (for example fire
neckline, fire damper, and so on.) or be introduced inside a pole accomplishing a FRL as per spec. C1.1 (or
120/120/120 where it is a room, for example, a substation);
4. Self-shutting -/60/30 fire ways to the entryways opening to the fire secluded stairs (take note of this
additionally incorporates the entrance ways to the condenser units on the plant stages).
Note that where fire dampers, fire collars, and so forth are utilised, recompense should be made for access
portals to be given inside the dividers/roofs to guarantee that upkeep get to is given.
Fire source highlight is characterized as;
a) The most distant limit of a street, waterway, lake or the like connecting a distribution,
b) The side or back limit of apportioning,
c) The outside mass of another expanding on the allocation which isn't a class 10 building
Question 4: Accessibility and Evacuation
The departure arrangements from the proposed building are given by:
1. Fire disengaged stairways (Farhan, Stefansen, Kazanci and Olesen, 2018)
2. Outside border entryways
The building is required to be served by at the very least 2 required ways out from each story as the building
has a powerful stature more prominent than 25m.
Other enumerating issues that should be tended to include:
Door Hardware
Exit entryway task
Stair construction
Handrail and balustrade construction
Details of Separation of rising and plummeting stairs
neckline, fire damper, and so on.) or be introduced inside a fire evaluated shaft accomplishing the required
FRL;
3. Any infiltration through a divider or room required to have a FRL (for example substation, engine
compartment, condo isolating divider and so forth.) is to be secured either by a tried model (for example fire
neckline, fire damper, and so on.) or be introduced inside a pole accomplishing a FRL as per spec. C1.1 (or
120/120/120 where it is a room, for example, a substation);
4. Self-shutting -/60/30 fire ways to the entryways opening to the fire secluded stairs (take note of this
additionally incorporates the entrance ways to the condenser units on the plant stages).
Note that where fire dampers, fire collars, and so forth are utilised, recompense should be made for access
portals to be given inside the dividers/roofs to guarantee that upkeep get to is given.
Fire source highlight is characterized as;
a) The most distant limit of a street, waterway, lake or the like connecting a distribution,
b) The side or back limit of apportioning,
c) The outside mass of another expanding on the allocation which isn't a class 10 building
Question 4: Accessibility and Evacuation
The departure arrangements from the proposed building are given by:
1. Fire disengaged stairways (Farhan, Stefansen, Kazanci and Olesen, 2018)
2. Outside border entryways
The building is required to be served by at the very least 2 required ways out from each story as the building
has a powerful stature more prominent than 25m.
Other enumerating issues that should be tended to include:
Door Hardware
Exit entryway task
Stair construction
Handrail and balustrade construction
Details of Separation of rising and plummeting stairs

Discharge from the Fire Isolated Exits
Details of departure arrangements to the Road
The areas of proposed ways out would seem to show that esteemed to fulfil prerequisites regarding travel
separations, removes between option ways out will require the documentation of an elective answer for fulfil
the execution necessities of BCA (Lin, Barooah, Meyn and Middelkoop, 2015).
The movement separations to ways out ought not to surpass:
Class 2
6m from an exit or from a point of decision
20m from a solitary exit at the dimension of departure to a street or open space
Alternate ways out not more than 45m separated
Travel separations to required ways out will be surpassed in following areas:
Private Levels:
Travel from passageway entryways of sole-inhabitance units to a point of decision surpasses 6m
(Measured up to approx. 8.0m) Block L1, L2 and L3 (Ashworth and Perera, 2015);
Travel from passage entryways of sole-inhabitance units to a point of decision surpasses 6m
(Measured up to approx. 12.5m) from Block M;
Porch Area (Level 01):
Travel separation to purpose of decision to elective ways out surpasses 20m;
Travel separate between elective ways out surpass 45m separated
Car park Levels:
Travel separation to required ways out surpasses 20.0m to purpose of decision to elective ways out (for
example estimated up to 30m);
Travel separations to required ways out surpass 40.0 (for example estimated up to 65m);
Distances between elective ways out surpass 60.0m (for example estimated up to 85m).
A fire designing arrangement will be required to address expanded travel separations (as distinguished
above) at construction declaration arrange (Crawford, Bartak, Stephan and Jensen, 2016).
Details of departure arrangements to the Road
The areas of proposed ways out would seem to show that esteemed to fulfil prerequisites regarding travel
separations, removes between option ways out will require the documentation of an elective answer for fulfil
the execution necessities of BCA (Lin, Barooah, Meyn and Middelkoop, 2015).
The movement separations to ways out ought not to surpass:
Class 2
6m from an exit or from a point of decision
20m from a solitary exit at the dimension of departure to a street or open space
Alternate ways out not more than 45m separated
Travel separations to required ways out will be surpassed in following areas:
Private Levels:
Travel from passageway entryways of sole-inhabitance units to a point of decision surpasses 6m
(Measured up to approx. 8.0m) Block L1, L2 and L3 (Ashworth and Perera, 2015);
Travel from passage entryways of sole-inhabitance units to a point of decision surpasses 6m
(Measured up to approx. 12.5m) from Block M;
Porch Area (Level 01):
Travel separation to purpose of decision to elective ways out surpasses 20m;
Travel separate between elective ways out surpass 45m separated
Car park Levels:
Travel separation to required ways out surpasses 20.0m to purpose of decision to elective ways out (for
example estimated up to 30m);
Travel separations to required ways out surpass 40.0 (for example estimated up to 65m);
Distances between elective ways out surpass 60.0m (for example estimated up to 85m).
A fire designing arrangement will be required to address expanded travel separations (as distinguished
above) at construction declaration arrange (Crawford, Bartak, Stephan and Jensen, 2016).
Paraphrase This Document
Need a fresh take? Get an instant paraphrase of this document with our AI Paraphraser

Dimensions of Exits
Least components of 1000mm and 2000mm tallness to be given inside ways out, with the ways of
movement ought to give a base width of 1000mm (take note of that all support get to, feline strolls, and so
on may agree to AS1657 in which case a 600mm clear width is required) (Ashworth and Perera, 2015).
The leave width gave inside each dimension of building is adequate measurement to serve the normal tenant
numbers. Required leave entryways should be point by point to swing toward departure from the building.
Entryways are allowed to contain a reasonable opening width of 750mm with a tallness of 1980mm as a
major aspect of departure necessities. Access for people with inabilities anyway requires a reasonable
entryway opening width of 850mm (for example least 870 mm entryways) (Bendix, 2017).
Question 5: Services and Equipment
Smoke risk management will be given all through the building by methods for the accompanying
frameworks:
Programmed Shutdown of Mechanical Systems as per the prerequisites of AS/NZS 1668.1-1998;
Programmed Smoke Detection and Alarm System as per the prerequisites of BCA Spec E2.2a and
AS 1670.1-2004 (Salet and Markus, 2015)
Programmed Pressurization to Fire Isolated Exits as per the prerequisites of AS/NZS 1668.1-1998
lift administrations
The traveller lifts to be introduced are to be: -
1. Fitted with notice signs, fire benefit controls as per AS 1735.2
2. Stretcher offices are to be furnished inside the lifts with least measurements of 600m wide, 2000mm
long and 1400mm high.
3. Something like two (2) crisis lifts with stretcher offices as per part E3.4 of BCA and AS 1735.2 must
serve each building with a successful tallness surpassing 50m
Light and ventilation
All through the advancement the arrangement of regular or mechanical ventilation is required to every
liveable room as per F4.5 Building Code of Australia also, AS 1668 and AS/NZS 3666.1.
Characteristic light should be given to every liveable room in a class 2 building.
Least components of 1000mm and 2000mm tallness to be given inside ways out, with the ways of
movement ought to give a base width of 1000mm (take note of that all support get to, feline strolls, and so
on may agree to AS1657 in which case a 600mm clear width is required) (Ashworth and Perera, 2015).
The leave width gave inside each dimension of building is adequate measurement to serve the normal tenant
numbers. Required leave entryways should be point by point to swing toward departure from the building.
Entryways are allowed to contain a reasonable opening width of 750mm with a tallness of 1980mm as a
major aspect of departure necessities. Access for people with inabilities anyway requires a reasonable
entryway opening width of 850mm (for example least 870 mm entryways) (Bendix, 2017).
Question 5: Services and Equipment
Smoke risk management will be given all through the building by methods for the accompanying
frameworks:
Programmed Shutdown of Mechanical Systems as per the prerequisites of AS/NZS 1668.1-1998;
Programmed Smoke Detection and Alarm System as per the prerequisites of BCA Spec E2.2a and
AS 1670.1-2004 (Salet and Markus, 2015)
Programmed Pressurization to Fire Isolated Exits as per the prerequisites of AS/NZS 1668.1-1998
lift administrations
The traveller lifts to be introduced are to be: -
1. Fitted with notice signs, fire benefit controls as per AS 1735.2
2. Stretcher offices are to be furnished inside the lifts with least measurements of 600m wide, 2000mm
long and 1400mm high.
3. Something like two (2) crisis lifts with stretcher offices as per part E3.4 of BCA and AS 1735.2 must
serve each building with a successful tallness surpassing 50m
Light and ventilation
All through the advancement the arrangement of regular or mechanical ventilation is required to every
liveable room as per F4.5 Building Code of Australia also, AS 1668 and AS/NZS 3666.1.
Characteristic light should be given to every liveable room in a class 2 building.

Question 6: Health and Amenity and Energy Efficiency
The proposed improvement will be furnished with protection building fixing and benefits as per NSW Part J
of BCA 2016. The considered to-fulfil arrangements of BCA just apply to warm protection in a class 2
building where advancement assent determines that protection is to be given as a major aspect of
advancement. The class 2 building will be liable to a Tecks Designers. We will depend upon the Tecks
Designers together with affirmation that duties made under BASIX have been joined into the plan before the
issue of Construction Certificate (Gyourko and Molloy, 2015).
The Class 2 (apartments) is furnished with sanitary facilities alongside laundry facilities that will fulfill the
arrangements of the BCA. Offices for workers comprising of storeroom skillet and washbasin must be given
in a different room at or close ground level and available to workers without entering a sole inhabitance unit.
This office is to be named as Accessible Unisex WC.
All through the development arrangement of characteristic or mechanical ventilation is required to every
single livable room as per F4.5 Building Code of Australia what's more, AS 1668 and AS/NZS 3666.1.
Natural light should be given to every tenable room in a class 2 building.
The sound transmission and protection necessities for Class 2 partitions will be furnished as per Part F 5 of
the BCA 2016. A report from a certified acoustic architect should be furnished to approve consistence with
the BCA.
The proposed improvement will be furnished with protection building fixing and benefits as per NSW Part J
of BCA 2016. The considered to-fulfil arrangements of BCA just apply to warm protection in a class 2
building where advancement assent determines that protection is to be given as a major aspect of
advancement. The class 2 building will be liable to a Tecks Designers. We will depend upon the Tecks
Designers together with affirmation that duties made under BASIX have been joined into the plan before the
issue of Construction Certificate (Gyourko and Molloy, 2015).
The Class 2 (apartments) is furnished with sanitary facilities alongside laundry facilities that will fulfill the
arrangements of the BCA. Offices for workers comprising of storeroom skillet and washbasin must be given
in a different room at or close ground level and available to workers without entering a sole inhabitance unit.
This office is to be named as Accessible Unisex WC.
All through the development arrangement of characteristic or mechanical ventilation is required to every
single livable room as per F4.5 Building Code of Australia what's more, AS 1668 and AS/NZS 3666.1.
Natural light should be given to every tenable room in a class 2 building.
The sound transmission and protection necessities for Class 2 partitions will be furnished as per Part F 5 of
the BCA 2016. A report from a certified acoustic architect should be furnished to approve consistence with
the BCA.

References
Allouhi, A., El Fouih, Y., Kousksou, T., Jamil, A., Zeraouli, Y. and Mourad, Y., 2015. Energy consumption
and efficiency in buildings: current status and future trends. Journal of Cleaner production, 109, pp.118-130
Ashworth, A. and Perera, S., 2015. Cost studies of buildings. Routledge
Bendix, R., 2017. Nation-building and citizenship: Studies of our changing social order. Routledge
Crawford, R.H., Bartak, E.L., Stephan, A. and Jensen, C.A., 2016. Evaluating the life cycle energy benefits
of energy efficiency regulations for buildings. Renewable and Sustainable Energy Reviews, 63, pp.435-451
Farhan, H., Stefansen, C., Kazanci, E.B.O.B. and Olesen, B.W., 2018. Simulation Study of Active Ceilings
with Phase Change Material in Office Buildings for Different National Building Regulations. In ASHRAE
2018 Winter Conference. American Society of Heating, Refrigerating and Air-Conditioning Engineers
Gyourko, J. and Molloy, R., 2015. Regulation and housing supply. In Handbook of regional and urban
economics (Vol. 5, pp. 1289-1337). Elsevier
Lin, Y., Barooah, P., Meyn, S. and Middelkoop, T., 2015. Experimental evaluation of frequency regulation
from commercial building HVAC systems. IEEE Transactions on Smart Grid, 6(2), pp.776-783
Rasmussen, B., 2018. Building acoustic regulations in Europe–Brief history and actual situation. In Baltic-
Nordic Acoustics Meeting 2018. Nordic Acoustic Association
Salet, W. and Markus, M., 2015. REGULATION DILEMMA Full Case studies Report
Zhang, T., Wan, M.P., Ng, B.F. and Yang, S., 2018, April. Model Predictive Control for Building Energy
Reduction and Temperature Regulation. In Green Technologies Conference (GreenTech), 2018 (pp. 100-
106). IEEE
Allouhi, A., El Fouih, Y., Kousksou, T., Jamil, A., Zeraouli, Y. and Mourad, Y., 2015. Energy consumption
and efficiency in buildings: current status and future trends. Journal of Cleaner production, 109, pp.118-130
Ashworth, A. and Perera, S., 2015. Cost studies of buildings. Routledge
Bendix, R., 2017. Nation-building and citizenship: Studies of our changing social order. Routledge
Crawford, R.H., Bartak, E.L., Stephan, A. and Jensen, C.A., 2016. Evaluating the life cycle energy benefits
of energy efficiency regulations for buildings. Renewable and Sustainable Energy Reviews, 63, pp.435-451
Farhan, H., Stefansen, C., Kazanci, E.B.O.B. and Olesen, B.W., 2018. Simulation Study of Active Ceilings
with Phase Change Material in Office Buildings for Different National Building Regulations. In ASHRAE
2018 Winter Conference. American Society of Heating, Refrigerating and Air-Conditioning Engineers
Gyourko, J. and Molloy, R., 2015. Regulation and housing supply. In Handbook of regional and urban
economics (Vol. 5, pp. 1289-1337). Elsevier
Lin, Y., Barooah, P., Meyn, S. and Middelkoop, T., 2015. Experimental evaluation of frequency regulation
from commercial building HVAC systems. IEEE Transactions on Smart Grid, 6(2), pp.776-783
Rasmussen, B., 2018. Building acoustic regulations in Europe–Brief history and actual situation. In Baltic-
Nordic Acoustics Meeting 2018. Nordic Acoustic Association
Salet, W. and Markus, M., 2015. REGULATION DILEMMA Full Case studies Report
Zhang, T., Wan, M.P., Ng, B.F. and Yang, S., 2018, April. Model Predictive Control for Building Energy
Reduction and Temperature Regulation. In Green Technologies Conference (GreenTech), 2018 (pp. 100-
106). IEEE