University Electrical Engineering Lab: Transformer Equivalent Circuit

Verified

Added on  2022/09/07

|19
|4460
|18
Practical Assignment
AI Summary
This assignment details a laboratory experiment focused on the analysis of a single-phase transformer's equivalent circuit. The experiment involves conducting open-circuit, short-circuit, and full-load tests on a 230V/230V, 50Hz, 100VA transformer. The open-circuit test is used to determine the turns ratio, magnetizing current characteristics, and the magnetizing components RM and XM. The short-circuit test is performed to find the primary-side winding resistance RSP and leakage inductance XSP. The full-load test examines the relationship between primary and secondary currents, and the assignment concludes with an on-load test to predict voltage regulation and efficiency. Calculations are performed to derive equivalent circuit parameters, and comparisons are made between predicted and measured values. The report includes detailed procedures, data tables, graphs, calculations, and analysis of the transformer's performance under various conditions.
Document Page
Figure 1 Transformer equivalent circuit
The secondary winding resistance and leakage inductance components RSS and XSS
can be referred to the primary side using the transformer turns-ratio, where they are
denoted by RSS and XSS respectively as shown in Figure 2.
Figure 2 Transformer equivalent circuit secondary components
referred to primary
Using the assumption that the magnitudes of the impedances RSP, XSP, RSS, XSS are
very much less than RM, XM, the elements RM and XM can be moved so that they
connect across the transformer input terminals. Consequently, RSS and XSS can be
lumped together with the primary-side impedances RSP and XSP to give the equivalent
components RS=RSP+RSS and XS=XSP+XSS, as shown by the equivalent circuit in
Figure 3,
1
tabler-icon-diamond-filled.svg

Secure Best Marks with AI Grader

Need help grading? Try our AI Grader for instant feedback on your assignments.
Document Page
Figure 3 Transformer equivalent circuit with lumped primary side
components RS and XS.
The Feedback laboratory equipment will be used to measure and calculate the
equivalent circuit parameters shown in Figure 3. Tests will be carried out on a
230V/230V, 50Hz, 100VA single-phase transformer.
2
Document Page
1. Transformer Equivalent circuit
The first part of the experiment will determine the parameters for the
equivalent circuit shown in Figure 4.
Make sure the ‘3 phase circuit breaker’ is in the off position and the ‘variable
output voltage’ is set to 0%, and then connect the Feedback equipment and
Voltech PM1000 power analyser as shown in Figure 4.
Figure 4 Schematic connection of the Feedback and Voltech equipment
The input Voltech PM1000 power analyser is connected so that the following
parameters can be measured:
V = transformer primary voltage
I = transformer primary current
W=input power (W)
p.f. = input power factor
The load Voltech PM1000 power analyser is connected so that the following
parameters can be measured:
V = transformer secondary voltage
I = transformer secondary current
W= load power (W)
p.f. = load power factor
3
V
I
VloVHi
AloAHi
V
I
VloVHi
AloAHi
Load
Variable ac
supply
Input power
analyser Load Power
analyser
Document Page
2. Transformer Open-Circuit Test
The first part of this test will establish the turns ratio NS/NP, the transformer
magnetising current characteristic and the magnetising components RM and
XM.
The switches on the three-phase resistive load 67-142, should be in the off
position so that the transformer secondary is open-circuit. On the Universal
Power Supply ensure the ‘variable output voltage’ control is set to 0%.
Set the ‘3 phase circuit breaker’ to the on position and then rotate the
‘variable output voltage’ in approximately 10% steps up to 100%.
Record the primary and secondary voltages and also the primary
current using the PM1000 power analysers, for each step.
Percentage
Setting %
Secondary Voltage
(V)
Primary Current
(mA)
0
13.14 14.2 5.6
10
38.4 31.6 10.24
20
58.8 63.85 12.4
30
87.7 95.3 14.7
40
113.1 103 16.8
50
135 146.8 18.8
60
161.5 175.6 21.4
70
184.4 200.8 24.3
80
210.5 209 29.3
90
235 250.5 36.7
100
248 269.8 45
Table 1 – Open circuit characteristics
Plot a graph of the transformer secondary voltage against the primary
voltage and determine the turns-ratio of the transformer from the
graph.
4
tabler-icon-diamond-filled.svg

Secure Best Marks with AI Grader

Need help grading? Try our AI Grader for instant feedback on your assignments.
Document Page
The relationship between primary, secondary and turns ratio is given
by the equation below
Vs / Vp = Ns /Np [1]………………1
Where Vs is the voltage at the secondary side of a transformer
Vp is the voltage at the primary side of a transformer
Ns is the number of turns at the secondary side
Np is the number of turns at the primary side
Multiplying both sides of equation 1 by Vp we get
Vs = (Ns /Np) * Vp……………2
Equation of a straight line is normally in the form of
y = mx + c
where m is the slope of the line and C is the intercept
Equation 2 represents the equation of the plotted line, therefore the
turns ratio is equivalent to the slope of the line.
Ns / Np = slope = (200-50) / (190 – 50) = 150 / 140
Turn ratio is thus 15 : 14
Compare and comment on the measured transformer secondary voltage
considering the rating of the transformer.
The voltage rating of the transformer is 230V, however the maximum
no load terminal voltage is slightly higher than the transformer ratings.
When the transformer is fully loaded, the rated current is drawn
through the secondary circuit, thus sufficient voltage drop. With the
secondary circuit open circuited, the no-load current is too small in
magnitude, resulting in little voltage drop, thus a higher terminal
voltage.
Plot the primary voltage against the primary (magnetising) current and
comment on the shape of the curve.
5
Document Page
The curve is divided into two regions; the linear region and saturation
region. In the linear region, magnetising current increases in direct
proportion to the primary voltage, the slope of the curve is steep. In
saturation region, the slope of the curve is less steep compared to linear
region. Transformation ratio of the transformer is distorted since the
secondary current is distorted by saturation of transformer core.
With the primary voltage set to 230V, record the primary voltage and
secondary voltage, and using the power analyser measure the primary
current and primary active power.
Primary Voltage
(V)
Primary Current
(mA)
Primary Power
(W)
230.5 35 4.89
Table 2 – Open circuit test results at nominal primary voltage.
From these measurements calculate the transformer equivalent core-
loss resistance RM and the magnetising reactance XM. Mark these
values on an equivalent circuit of the transformer. Hint - use the
equation , where P is the active power, V and I are the
primary voltage and current and M is the phase angle between the
voltage and current. Separate the primary current into resistive and
inductive components and hence calculate RM and XM.
P0 = V1 I0 Cos M
Where V1 and I0 are primary voltage and current respectively
The power factor at no load is thus
Cos M = P / VI
Substituting the values of power, current and voltage we get
= 4.89 / (230.5 * 0.035)
= 0.60614
6
Document Page
Resistive component of primary current is
IR = P0 / V1
= I0 Cos M
= 35 * 0.60614
= 21.22 mA
Inductive component of the primary current[2]
II = sqrt (I02– IR2)
= sqrt (352– 21.222)
= 27.834 mA
Equivalent core loss resistance Rm is
RM = V1 / IR
= 230.5 / 0.02122
= 10.862kΩ
Magnetising reactance Xm is
XM = V1 / II
= 230.5 / 0.027834
= 8.281 kΩ
3. Transformer Short-Circuit Test
This test will be used to determine the primary-side winding resistance RSP and
leakage inductance XSP. For this test the secondary of the transformer is to be
connected as a short circuit. Make sure the ‘3 phase circuit breaker’ is in the
off position and the ‘variable output voltage’ is set to 0%, and connect the
short-circuit link as shown in Figure 5.
Figure 5 Short-circuit connection of the transformer
7
V
I
VloVHi
AloAHi
V
I
VloVHi
AloAHi
Load
Variable ac
supply
Input power
analyser Load Power
analyser
Short-circuit
link
tabler-icon-diamond-filled.svg

Paraphrase This Document

Need a fresh take? Get an instant paraphrase of this document with our AI Paraphraser
Document Page
Ask the laboratory supervisor to check your circuit before
continuing.
If you have not already done so, calculate the value of the transformer
rated current.
Set the ‘3 phase circuit breaker’ to the on position and slowly rotate the
‘variable output voltage’ until the secondary current is equal to its rated
current. The ‘variable output voltage’ control should be set at just
under 10%, if you are unable to generate the required secondary
current with the supply control in this position, seek assistance from
the laboratory supervisor.
Record the primary voltage and using the input power analyser, record
the primary current and the primary input power, and then switch off
the ‘3 phase circuit breaker’ and remove the short-circuit.
Primary Voltage
(V)
Primary Current
(mA)
Primary Power
(W)
25.68 477.6 8.6
Table 3 – Short circuit test results at full-rated current flow.
From these measurements calculate the transformer equivalent winding
resistance RS and leakage reactance XS. Mark these values on an
equivalent circuit of the transformer.
Power factor during this test is given by
p.f = Cos = P / VI
= 8.6 / (0.4776 * 25.68)
= 0.7012 lagging
Phase angle, ∅ = 45.48
Series Impedance, Z is given by
Z = (V / I) <
= (25.68 / 0.4776) < 45.48
= 53.77 < 45.480
= 37.7 + j38.34
Rs = 37.7 Ω
Xs = 38.34Ω
8
Document Page
4. Transformer Full-Load Test
The next part of the experiment will examine the relationship between the
transformer primary and secondary currents. The Switched Three-Phase
Resistive 67-142 is to be used to load the transformer secondary. The three
switches in this unit can be used to connect the three resistors 950, 1950
and 3770 in parallel.
Calculate the load resistance for the transformer that would be required to
draw rated current from the secondary. Hence calculate the settings of the
three-phase load resistor switches that would give approximately (within a few
percent) rated current.
Transformer ratings
Voltage ratings 230V/230V
S = 100VA
Secondary voltage is 230 V
Rated current, I = S / V = 100 / 230
= 0.4348A
Maximum load current is thus 0.4348
Load resistance = Voltage across the secondary terminals / load current
= 528.98 Ω
Load resistor settings
950Ω resistor – 530 / 950 = 56 %
1950 resistor – 530 / 1950 = 27 %
3770 resistor – 530 / 3770 = 14 %
Check that the secondary short-circuit has been removed, and the ‘variable
output voltage’ is set to 0%. Close the circuit breaker and set the transformer
primary voltage to 230V and with an open-circuit secondary re-record the
primary current using the power analyser. Switch in the rated load resistance
as calculated in the previous exercise, and record the primary and secondary
transformer parameters.
9
Document Page
The ideal transformer equation relates the primary and secondary currents
using its turns-ratio. Using this equation, compute the predicted value of the
transformer, on-load primary current based on the measured on-load
secondary current. Compare and comment on the predicted and measured
values of the on-load secondary current, and if required, use further
calculations to justify any discrepancies.
Turns ratio Ns /Np = Ip / Is
Predicted on load primary current from the equation above is given by
Ip = Ns / Np * Is
From open circuit test Ns / Np = 15/14 and measured value of secondary
voltage, Is = 423 mA
Ip = 15 / 14 * 423
= 453 mA
There is a difference between predicted value and the measured value of the
secondary voltage. Calculation of transformer voltages using turn ratio is
based on the assumption that phase angles of primary and secondary winding
are equal. The total current drawn from the power supply by the primary
winding is actually the vector sum of no load current and additional supply
current as a result of a load connected to its secondary terminals[3].
Off-load Primary current
(mA)
35.3
Full-load Primary Current
(mA)
484
Full Load Secondary Current
(mA)
423
Table 4 – Full-load Current Balance
5. Transformer on-Load Test (Voltage Regulation & Efficiency)
We will now use the equivalent circuit model of the transformer to predict the
voltage regulation and efficiency of the transformer on-load.
Check that the secondary short-circuit has been removed, and the
‘variable output voltage’ is set to 0%. Set the ‘3 phase circuit breaker’
to the on position and then set the ‘variable output voltage’ to give the
full rated primary voltage of 230V.
With the secondary open-circuit, measure the secondary voltage.
Switch on the resistive load to give approximately rated current into
the load, and measure the primary voltage and current and the
secondary voltage and current. Using the power analysers, measure the
primary and secondary power.
Off-Load Secondary Voltage
(V)
250
10
tabler-icon-diamond-filled.svg

Secure Best Marks with AI Grader

Need help grading? Try our AI Grader for instant feedback on your assignments.
Document Page
Primary voltage (on-
load) (V)
Primary Current
(mA)
W1
(W)
229.3
481.3 109.5
Secondary voltage
(on-load) (V)
Secondary Current
(mA)
W2
(W)
229.3 421.0 96.2
Table 5 – Regulation data at full resistive loading
From these measurements, calculate the percentage voltage regulation
of the transformer and the transformer efficiency. Use your equivalent
circuit model to predict the voltage regulation and efficiency of the
transformer for the given load condition, and compare these values
with those measured in the experiment where,
Voltage regulation from data measured in the lab
= (250 – 229.3) / 250 * 100
= 8. 28 %
Voltage regulation from equivalent circuit model
where,
IS = secondary current
= power factor angle of the load (inductive)
= RS referred to the secondary side
= XS referred to the secondary side
Rs and Xs from equivalent circuit model are
Rs = 37.7Ω
Xs = 38.34
R/S = 37.7 * 15/14
= 40.4Ω
X/S = 38.34 * 15/14
= 41.08Ω
For resistive loading power factor is 1
11
Document Page
= cos-1 (1)
= 0
Is = 0.421
= 6.8 %
Efficiency computation using measured values
= 96.2 / 109.5 * 100
= 87.85%
Efficiency computation using equivalent model
Losses - core losses = Vp2 / Rm = 2302 / 10834
= 4.883 W
- Copper losses = Is2 * R/s = 0.4212 * 40.4
= 7.16
= 88.87 %
Efficiency and voltage regulation computed using equivalent circuit model
and those computed using measured values are nearly the same. The
variation is due to errors in taking measurement and the fact that the
equivalent circuit model is based on approximation[5].
Turn the ‘variable output voltage’ to 0% and switch the ‘3 phase circuit
breaker’ off and connect a 1.71H inductor in series with the resistive
load using the ‘three-phase inductive load’.
Set the ‘3 phase circuit breaker’ to the on position and then set the
‘variable output voltage’ to give the full rated primary voltage of
230V.
With the secondary open-circuit, measure the secondary voltage.
Switch on the load and measure the primary voltage, current and power
and the secondary voltage, current and power.
Off-Load Secondary Voltage
(V)
250.9
Primary voltage (on-
load) (V)
Primary Current
(mA)
W1
(W)
230
333 55.9
12
Document Page
Secondary voltage
(on-load) (V)
Secondary Current
(mA)
W2
(W)
230.5 276.2 47.9
Table 6 – Regulation data for resistive and inductive loading
Again, calculate the percentage voltage regulation and efficiency of the
transformer and compare these values with those predicted by the
equivalent circuit model.
Voltage regulation from data measured in the lab
= (250.9 – 230.5) / 250.9 * 100
= 8.13 %
Voltage regulation from equivalent circuit model
where,
IS = secondary current
= power factor angle of the load (inductive)
= RS referred to the secondary side
= XS referred to the secondary side
Rs and Xs from equivalent circuit model are
Rs = 37.7Ω
Xs = 38.34
R/S = 37.7 * 15/14
= 40.4Ω
X/S = 38.34 * 15/14
= 41.08Ω
Power factor is calculated using the formula below
Po = V * I cos ()
cos () = Po / V * I
= 47.9 / 230.5 * 0.2762
= 0.75 lagging
= cos-1 (0.75)
= 41.41
Is = 0.2762
13
tabler-icon-diamond-filled.svg

Paraphrase This Document

Need a fresh take? Get an instant paraphrase of this document with our AI Paraphraser
Document Page
= 6.33 %
Efficiency computation using measured values
= 47.9 / 55.9 * 100
= 85.69 %
Efficiency computation using equivalent model
Losses - core losses = Vp2 / Rm = 2302 / 10834
= 4.883 W
- Copper losses = Is2 * R/s = 0.27622 * 40.4
= 3.08W
= 85.74 %
Efficiency and voltage regulation computed using equivalent circuit model
and those computed using measured values are nearly the same. The
variation is due to errors in taking measurement and the fact that the
equivalent circuit model is based on approximation[4].
Turn the ‘variable output voltage’ to 0% and switch the ‘3 phase circuit
breaker’ off and replace the inductive load with a 7F capacitor, to
give a series resistive/capacitive load.
Set the ‘3 phase circuit breaker’ to the on position and then set the
‘variable output voltage’ to give the full rated primary voltage of
230V.
With the secondary open-circuit, measure the secondary voltage.
Switch on the load and measure the primary voltage, current and power
and the secondary voltage, current and power.
Off-Load Secondary Voltage
(V)
250.2
Primary voltage (on-
load) (V)
Primary Current
(mA)
W1
(W)
229.6
379 75.95
14
Document Page
Secondary voltage
(on-load) (V)
Secondary Current
(mA)
W2
(W)
246.3
343.8 65.72
Table 7 – Regulation data for resistive and capacitive loading
Again, calculate the percentage voltage regulation and efficiency of the
transformer and compare these values with those predicted by the
equivalent circuit model – Be careful you ensure that the sign of the
load power factor angle
, is correct.
Voltage regulation from data measured in the lab
= (250.2 – 246.3) / 250.2 * 100
= 1.558 %
Voltage regulation from equivalent circuit model
where,
IS = secondary current
= power factor angle of the load (inductive)
= RS referred to the secondary side
= XS referred to the secondary side
Rs and Xs from equivalent circuit model are
Rs = 37.7Ω
Xs = 38.34
R/S = 37.7 * 15/14
= 40.4Ω
X/S = 38.34 * 15/14
= 41.08Ω
Power factor is calculated using the formula below
Po = V * I cos ()
cos () = Po / V * I
= 65.72 / 246.3 * 0.3438
= 0.776 leading
= cos-1 (0.776)
= 39.1
Is = 0.3438
15
Document Page
= 0.75 %
Efficiency computation using measured values
= 65.72 / 75.95 * 100
= 86.53 %
Efficiency computation using equivalent circuit model
Losses - core losses = Vp2 / Rm = 2302 / 10834
= 4.883 W
- Copper losses = Is2 * R/s = 0.34382 * 40.4
= 4.78W
= 87.2 %
Efficiency and voltage regulation computed using equivalent circuit model
and those computed using measured values are nearly the same. The
variation is due to errors in taking measurement and the fact that the
equivalent circuit model is based on approximation.
Compare and comment on the voltage regulation for the purely
resistive load, the resistive/inductive load and the resistive/capacitive
load.
The transformer secondary voltage varies depending on the load
connected on its terminals. The secondary voltage also depends on
whether the power factor is leading, lagging or resistive. Voltage
regulation gives an indication on how the transformer will behave
under different loads. The smaller the percentage of voltage regulation,
the smaller the variation between the secondary voltage and the load.
Therefore, smallest voltage regulation percentage is desirable. Of the
three load combinations, resistive/capacitive load has the lowest
voltage regulation compared to resistive and resistive/inductive load,
thus its healthy to the system.
6 Determination of operating point of maximum efficiency
The purpose of the last part of this experiment is to plot the change of
transformer efficiency with load and to determine the operating point
of maximum efficiency and the conditions under which this point will
occur.
16
tabler-icon-diamond-filled.svg

Secure Best Marks with AI Grader

Need help grading? Try our AI Grader for instant feedback on your assignments.
Document Page
With the circuit breaker in the open position, connect the secondary of
the transformer across the resistive load, with all load switches in the
open position.
Ensuring that the ‘variable output voltage’ is set to 0%. Set the ‘3
phase circuit breaker’ to the on position and then set the ‘variable
output voltage’ to give the full rated primary voltage of 230V.
Turn the load switches on in the sequence shown in the table below (x
represents a closed switch). In each case, record the secondary current,
primary and secondary power readings and hence calculate the
efficiency of the transformer at each point.
3770Ω 1950Ω 950Ω I2
(mA)
W1
(Watts)
W2
(Watts)
Efficiency
(%)
X
128 21.9 16.8 76.7
X
128.8 37 30.7 83.0
X X
191.6 52.8 46.2 87.5
X
298.7 67 59.3 88.5
X X
308.6 81.8 77.5 95.1
X X
364 95.4 84.6 88.7
X X X
421.7 109.8 96.5 87.9
Table 8 – Resistive loading data
Plot the efficiency against secondary current and determine the fraction
of rated current at which maximum efficiency is observed. Given that
the Wattmeter reading during the open-circuit test represents the
transformer iron loss, comment on the relative values of iron and
copper loss at the point of maximum efficiency.
17
Document Page
The secondary current at maximum efficiency is equal to 0.31A, this is
the highest percentage of the rated current. This implies that the
efficiency of a transformer is maximum when operated at rated current.
Efficiency of the transformer during the open circuit test is poor, this is
attributed to the iron loss that causes a drop in the efficiency. The
transformer efficiency is maximum when the value of copper losses is
equal to that iron losses[5].
18
Document Page
REFERENCES
[1] S. Chapman, Electric Machinery Fundamentals. New York: McGraw-Hill,
2012
[2] M. Patel, Introduction To Electrical Power And Power Electronics. Boca
Raton, FL: CRC Press, 2013.
[3] T. Galvão and D. Simonetti, A Low-Power Setup Proposal for Power
Transformer Loading Tests. Energies, 12(21), p.4133, 2019.
[4] S. Lakervi, Evaluation of Transformer Loading Above Nameplate
Rating. Electric Machines & Power Systems, 28(7), pp.625-636, 2016.
[5] R. Mehta and V. Mehta, Principles Of Electrical Machines. New Delhi: S.
Chand & Co., 2014
19
chevron_up_icon
1 out of 19
circle_padding
hide_on_mobile
zoom_out_icon
logo.png

Your All-in-One AI-Powered Toolkit for Academic Success.

Available 24*7 on WhatsApp / Email

[object Object]